VZP-U_vyh-I_vyh-rs-AB-UKHL4 Single-channel rectifier with AB control unit and ATS unit

The rectifier is equipped with an LCD display and LED indication on the door, RS485 ModBus RTU interface, discrete status outputs. Contains an external AB current control unit (optionally voltage), a backup network input unit, one step-down low-frequency transformer, protective input and output circuit breakers (can optionally be replaced with a disconnector), a rectifier power unit, a reverse diode.
Description

Purpose 

Designed to charge acid or alkaline storage batteries and supply DC consumers. Can be used to supply DC voltage to operational circuits of complete substations and distribution points, emergency power supply systems of power supply devices. Similar devices can be connected to parallel operation for a common load and used in circuits with parallel redundancy. The devices are made with microprocessor control and have a built-in control and signaling system. Features

Features

  • Natural cooling of the power unit and transformer;
  • High overload capacity and fault tolerance;
  • Galvanic isolation of DC circuits;
  • Ability to work with sealed and classic storage batteries;
  • Two-stage (I/U) battery charge, buffer recharging mode with temperature compensation;
  • LCD display and push-button panel for entering VZP parameters on the cabinet door;
  • Remote monitoring of the status via digital interface RS485, Ethernet;

Operating conditions

  • Ambient temperature from -10 to +40°С, UHL3 versions with heating are possible;
  • Relative air humidity up to 80% at +25°С;
  • Storage temperature from minus 50 to plus 40°С;
  • Working position in space – vertical;

Main technical characteristics

NameValue
Phase number3
Nominal line voltage, V220/380
Input voltage variation range, %-15/+15
Nominal AC frequency, Hz50
Power factor at nominal output parameters, not less than0,9
Nominal DC voltage, V24, 48, 60, 110, 220, 260
Nominal DC output current, A10, 40, 80, 160, 180, 200
DC voltage regulation range(0,1…1,2)UnOhm
Voltage stabilization accuracy, not more than, %0,5
Output current stabilization accuracy, not more than, %1
Operating modeContinuous
Protection classIP21, IP31
Service life, years20